- Data Centre Construction — equipment-nameplate OCR checked against the equipment schedule
- Why this exists
- How it works
- Fields extracted (35)
- Equipment types recognised (55)
- Server racks — a first-class subsection
- Results
- Comparison with related models
- Fine-tuning — the higher-accuracy server model
- Intended use
- Limitations
- Quickstart
- Evaluation & reproducibility
- Repository contents
- Provenance
- Safety
- Licence and trademarks
- Citation
- Why this exists
Data Centre Construction — equipment-nameplate OCR checked against the equipment schedule
Constructelligence is developing frontier construction-AI models. This kit is the lite, open tier — released for research and evaluation; the company's flagship production models are a separate, larger tier (see constructelligence.co).
Read an equipment nameplate and know if it is the unit the schedule asked for. Point a phone at the nameplate of a UPS, PDU, switchgear, generator, transformer, busway, battery, CRAH, chiller — or a server rack — and the engine returns the plate's fields (35 of them, grouped Identification / Electrical / Cooling / Server racks / Mechanical) and checks each one against the equipment schedule, flagging a mismatch instead of a silent pass. It builds an asset register and exports it to CSV.
Built for the part of a data-centre job where the gear is the job. The expensive mistakes are a unit delivered at the wrong voltage or rating, or one that quietly never makes it onto the asset register.
Runs on the device. OCR, extraction and matching run in the browser (or Node) with no server and no upload. A nameplate photo of live infrastructure never leaves the phone that took it — no GPU, no key, no data egress.
▶ Try it live: huggingface.co/spaces/constructelligence/data-centre-nameplates — a browser demo with a sample schedule and sample plates.
| Task | Image → structured nameplate fields → schedule verification |
| Fields | 35, in five groups (Identification, Electrical, Cooling, Server racks/IT, Mechanical) |
| Equipment | 55 types, device wording ranked above family (see below) |
| OCR | Tesseract.js 5 (English LSTM), pretrained — no fine-tuning |
| Extraction | Deterministic labelled-field parser + OCR error model + numeric range guards |
| Matching | Code folding (O/0, I/L/1, S/5, B/8, Z/2) + voltage-compatibility signal |
| Quality gate | Advisory photo check (blur, glare, darkness, resolution) before OCR |
| Runtime | Browser · Node · edge — no GPU, no server, no data egress |
| Field accuracy | 99.8% clean / 80.0% under character-error stress (extraction benchmark) |
| Licence | Apache-2.0 |
Why this exists
General OCR reads the text on a nameplate. A commissioning or QA team needs the text to answer a narrower question: is this the right unit, and does it match what was specified? That means three things a plain OCR call does not do:
- Turn plate text into fields, not paragraphs. "INPUT: 480Y/277 VAC 3 PH 60 HZ" becomes
voltage=480Y/277 V,phase=3,hz=60; "RATING: 750 KVA / 675 KW" becomeskva=750,kw=675. - Survive the way OCR misreads plate lettering. Serifed
V→Vv,K→X(XVA),HZ→Hw, codes split after their punctuation (NPX- 750- 480). The parser repairs these before matching, and rejects out-of-range noise (0 KVA, a stray0amp) rather than recording it. - Compare to the schedule the way codes actually differ. Model and serial codes are compared with
O/0,I/L/1,S/5,B/8,Z/2folded and punctuation ignored, so a misread is not a false mismatch, while a genuine voltage variant (NPX-750-415vsNPX-750-480) still fails. A voltage a plate and a schedule row share is a positive signal; the equipment type still wins ties, so a 415 V UPS plate is not matched to a same-voltage PDU.
The result is a pass/mismatch verdict per plate, with the fields that disagree named.
How it works
photo ─► photo check ─► OCR (Tesseract.js) ─► field parser ─► equipment typing ─► schedule matcher ─► verdict + CSV
blur/glare lines + confidence labelled rules maker line excluded code folding, voltage signal
- Photo check — an advisory blur/glare/darkness/resolution read before OCR; the shot can be retaken before a bad read.
- OCR (
tesseract.js@5, English) returns lines with a per-line confidence; two page-segmentation passes are merged field by field when the first is weak. - Field parser scans lines for labelled values (
MODEL,S/N,MVA,MCA,MOCP,FLA,VOLTS,REFRIGERANT,MFG DATE, …), reading voltages as480Y/277,13.8 kV,208/120, and rejecting look-alikes. Numeric fields are range-guarded. Lines OCR scored near zero are dropped first. - Equipment typing recognises 55 families and ranks the specific device above its family (flywheel before UPS; paralleling gear before generator; dry cooler before chiller; rack before server). The maker line is excluded from typing, so a vendor called “…Transformer Corp” cannot type a chiller plate.
- Schedule matcher ranks candidate tags — a serial match wins outright; otherwise model similarity dominates, with manufacturer, equipment type and a compatible voltage as signals. Among equal matches the first unscanned tag is offered.
- Field checks compare the reading to the chosen row (
ok/mismatch/unreadper field) and return an overall status:verified,partial,mismatch,unmatchedormissing(scheduled but not scanned).
Fields extracted (35)
Identification — manufacturer, model, serial, mfgDate
Electrical
| Field | Example | Notes |
|---|---|---|
voltage |
480Y/277 V | every voltage on the plate; 13.8 kV, 208/120, 480 |
phase / hz |
3 / 60 | PH/PHASE/Ø; 50 or 60 Hz |
kva / kw |
750 / 675 | kVA, KW, EKW; thousands separators |
amps |
1002 | labelled FLA/RLA/CURRENT/AMPS first |
pf |
0.8 | power factor, 0–1 |
mca / mocp |
612 / 800 | min circuit ampacity; max overcurrent protection |
sccr |
65 | short-circuit / interrupting rating (kAIC) |
enclosure |
NEMA 3R | NEMA type or IEC IP code |
standards |
UL 1989 | UL / IEC / ANSI / IEEE / NFPA / CSA / EN listings |
batteryType |
VRLA | VRLA, AGM, Gel, Flooded, Li-ion, LiFePO4, NiCd, Lead-acid |
batteryAh / cells |
500 / 48 | amp-hours; cell count |
Cooling — refrigerant, charge, tons, btu, cfm, gpm
Server racks / IT — uHeight (rack U, incl. "42RU"), formFactor (blade / tower / a labelled "2U"),
powerW, rackLoad (static/dynamic load, kg), outletTypes (canonical outlet mix, e.g. C13x12 C19x4),
outlets, portSpeed (fastest link, GbE), ports
Mechanical — rpm, weight (normalised to kg)
Equipment types recognised (55)
Power: flywheel · UPS · STS · ATS · rectifier/DC · inverter · BESS · nitrogen generator · paralleling gear · generator · fuel system · switchgear/switchboard · MCC · metering/CT · protective relay · transformer/DGA monitor · SPD · capacitor/PFC · neutral grounding resistor · VFD · busway · panelboard · PDU/RPP · battery · load bank
Cooling & mechanical: heat pump · pump · cooling tower · thermal storage · chiller · dry cooler/condenser · CDU · CRAH/CRAC · AHU · heat exchanger · expansion tank · air separator · boiler · humidifier · water treatment · air dryer · compressor · fan coil · rooftop unit · makeup air · economizer
Fire, safety & controls: fire suppression · fire alarm · leak/gas detection · BMS/EPMS/DCIM
IT & white space: rack · server/storage · network gear · KVM/console
Server racks — a first-class subsection
Racks, rack PDUs, switches and in-row cooling are what the electrical and cooling design actually serves, so
they are treated as data-centre equipment, not an afterthought: Rack U, Form factor, Power (W),
Rack load (kg), Outlet mix, PDU outlets, Port speed (GbE) and Ports are extracted and checked like any
other field, and the equipment set covers rack/enclosure, server, network, KVM and rack PDU. Sample plates
include a PowerEdge-class server, a rack PDU with a C13/C19 outlet mix, a 25G switch and a blade chassis with a
static floor load.
Results
Extraction benchmark — labelled plates, field by field
A generated corpus of plates with by-construction ground truth (not the parser's own reading), rendered
with wording variety. clean isolates the extractor + matcher; ocr adds the character errors OCR makes on
plate lettering. n = 1000. Reproduce with node tests/nameplates-extraction-bench.mjs --n=1000.
| Condition | Exact plate | Micro-F1 | ms/plate |
|---|---|---|---|
| clean | 94.1% | 99.7% | 0.49 |
| ocr (character-error stress) | 1.1% | 79.9% | 0.49 |
Per-field F1 is 100% for manufacturer, type, model, serial, kVA, phase, Hz, MCA, MOCP, refrigerant,
pf, cfm, uHeight, sccr and enclosure in the clean condition; the residual clean misses are a small number of
voltage and mfgDate cases. The ocr condition is deliberately harsh (per-character flips); low-confidence
fields are surfaced for a human rather than trusted. Per-field tables: eval/extraction-bench.json.
OCR benchmark — drawn plates through phone-photo degradations
Plates drawn for several equipment types, each pushed through real-photo degradations (small, blurred, noisy,
low-contrast, glare, tilted, keystoned, dark anodised, JPEG, plate-small-in-scene, sideways, and a "phone"
composite), then run through the app's own OCR + parser and scored field by field. An earlier run over six
plate types and 13 conditions scored 99.9% overall (727/728); the harness now draws more plate types and
is re-run on release. Run it with node tests/nameplates-bench.mjs (needs a browser for Tesseract.js).
Read this honestly. These are machine-drawn plates. A real plate on a live unit is harder: cast shadows, embossed lettering, print over brushed metal, a plate half out of frame. Expect the degradation suite, not the clean row, and treat every low-confidence field as one a person must confirm.
Comparison with related models
Nameplate extraction has no shared public benchmark — FUNSD/CORD measure invoices and forms, not equipment
plates. These are the closest published reference points, on their own datasets; they are context, not a
head-to-head. The only directly comparable scores are ones produced by the corpus in
ml/nameplates/bench/.
| Model / method | Task & dataset | Reported |
|---|---|---|
| This engine | named-field extraction, own labelled plate corpus | 99.7% micro-F1 (clean) |
| LayoutLMv3 (base) | entity extraction, FUNSD | 92.08 F1 |
| LiLT | entity extraction, FUNSD | 88.41 F1 |
| Donut | field extraction, CORD | 84.1 F1 |
| CTPN + Transformer | power-equipment nameplate detection / recognition | 88.7% det F1 · 92.3% char acc |
| PP-OCRv4 (TL-DREN) | electricity nameplate detection / recognition | 0.524 det F1 · 0.82 rec acc |
| RNN nameplate OCR | power-equipment nameplate chars (zh + alnum) | 99.9% zh · 99.3% alnum |
| OCR-free VLM (e.g. Qwen2.5-VL-7B) | document KIE, zero-shot | varies; strong but large |
What is different here: the engine is small, deterministic, on-device, and schedule-aware. It does not
just transcribe a plate — it decides verified / mismatch against a schedule and names the fields that
disagree, which no general document model does out of the box.
Fine-tuning — the higher-accuracy server model
Alongside the on-device path, a Donut model
(naver-clova-ix/donut-base) is fine-tuned to read a plate
straight into fields (<s_nameplate><s_type>ups</s_type><s_manufacturer>…) for a server / endpoint where
the browser engine falls short. Training data is synthetic plates with real-photo degradations plus corrected
real plates; best checkpoints are selected by field accuracy, using the same OCR-aware comparison the app
uses. The corpus in ml/nameplates/bench/ scores it on the same test set as the on-device engine.
Nothing on this page claims the accuracy of that model yet — it is the roadmap, not a result.
Intended use
- Commissioning and QA walks: photograph each unit as it is installed; confirm the delivered unit matches the equipment schedule; capture an asset register as you go.
- Receiving and delivery checks: flag the unit that arrived at the wrong voltage or rating before it is set.
- Register completion: track scheduled tags that have no plate scanned against them yet.
- Takeoff and submittal review: pull model/rating fields off a plate photo into a spreadsheet.
Out of scope — do not use it for
- Safety, code compliance or energisation decisions. It reads a plate; it does not verify that a unit is safe to energise, correctly protected, or code-compliant.
- An as-built or a legal record on its own. OCR misreads happen; low-confidence fields are highlighted and any field that disagrees with the schedule must be confirmed by eye.
- Serial-number evidence in a dispute without human verification; the register flags duplicate serials but cannot tell a repeated plate from a copied number.
Limitations
- English nameplates, Latin script. Non-Latin or handwritten plates are out of scope.
- Glare, blur and angle degrade OCR. The parser repairs common misreads, but a badly glared or very
low-contrast plate will lose fields (those come back
unread, not invented). - Deterministic parser, not a language model. It reports only what it can match to a rule; it will not infer a missing digit.
- The schedule must be structured (CSV with a Tag or Model column). Free-form schedule PDFs are not parsed here.
Quickstart
The engine is plain ES modules with no build step. nameplate-model.js is the extractor and verifier;
schedule-import.js is the CSV reader it depends on.
import { parseNameplate, parseEquipmentSchedule, candidatesFor, checkAgainst, statusOf } from './nameplate-model.js';
const reading = parseNameplate(`NORTHLINE POWER SYSTEMS
UNINTERRUPTIBLE POWER SUPPLY
MODEL NO: NPX-750-480
SERIAL NO: NL26A01937
INPUT: 480Y/277 VAC 3 PH 60 HZ
RATING: 750 KVA / 675 KW
INPUT CURRENT: 1002 A
MFG DATE: 03/2026`);
console.log(reading.type); // 'ups'
console.log(reading.fields.voltage); // { value: '480Y/277 V', values: [480, 277], conf, line }
const { items } = parseEquipmentSchedule(scheduleCsv);
const [best] = candidatesFor(reading, items);
console.log(statusOf(checkAgainst(reading, best.item), best.item.tag)); // 'verified' | 'partial' | 'mismatch' | …
In a browser, feed Tesseract's data.lines ([{ text, confidence, bbox }]) straight into parseNameplate to
keep OCR confidence and the plate line each value came from.
Evaluation & reproducibility
- Extraction:
node tests/nameplates-extraction-bench.mjs --n=1000 --json=…— labelled corpus, per-field precision/recall/F1, whole-plate exact match, ms/plate. Corpus dump for other models:… --dump=…/extraction-corpus.jsonl. Method and comparator:ml/nameplates/bench/README.md. - Unit tests: the parser, voltage reader, code folding, schedule parsing, candidate ranking, mismatch
detection, range guards and the matcher —
node --test tests/nameplate-model.test.mjs(all passing). - OCR end-to-end:
node tests/nameplates-bench.mjs— drawn plates through phone-photo degradations. - Fine-tuned reader:
ml/nameplates/cloud/eval_donut.pyscores the Donut model field by field on the held-out split.
Repository contents
| File | What it is |
|---|---|
nameplate-model.js |
the extractor, matcher and register builder (ES module) |
schedule-import.js |
the CSV schedule reader it depends on |
progress-project.js |
a helper the schedule reader imports |
sample_schedule.csv |
a 10-row data-centre equipment schedule |
sample_plates.json |
sample plates: a match, a flagged mismatch, a switchboard, a server |
eval/ |
OCR benchmark output, extraction benchmark output and corpus |
config.json |
machine-readable fields, groups, types and statuses |
Provenance
An open extraction and verification engine from Constructelligence, the same code path that powers the
Data Centre Construction mode of BuildVision. No customer data is used; sample plates use fictional
makers and models.
It is the document-AI sibling of the vision models
construction-site-safety-hazards
and electrical-circuit-connectivity.
Safety
This is a prompt to look, not a finding. It is not safety-rated, not a compliance decision, and not a substitute for inspection by a competent person. Verify every flagged field against the physical plate before acting on it.
Licence and trademarks
Code released under Apache-2.0. Brand and product names (Schneider Electric, Eaton, Vertiv, Caterpillar, Trane, Dell, Cisco, …) are trademarks of their owners and are matched only to identify user-supplied plates; this project is independent and not affiliated with or endorsed by them.
Citation
@misc{constructelligence_nameplates,
title = {Data Centre Construction: equipment-nameplate OCR checked against the equipment schedule},
author = {Constructelligence},
year = {2026},
howpublished = {\url{https://huggingface.co/constructelligence/data-centre-nameplates}}
}